GD350A series high-performance multifunction VFD
-251-
Function
code
Name
Description
Default Modify
P28.05
Speed/torque mode
switching frequency
point in
master/slave mode
2
0.00–10.00Hz
5.00Hz
○
P28.06
Slave count
0–15
1
◎
P28.07–
P28.24
Reserved
0–65535
0
○
P28.25 Fire mode function
0: Invalid
1: Fire mode 1
2: Fire mode 2
When P90.00=0, the fire mode is invalid, and
the normal running mode is used. In this case,
the VFD stops when encountering a fault.
When the fire mode is valid, the VFD runs at
the speed specified by P90.01.
When fire mode 1 is selected, the VFD runs
always except when the VFD has been
damaged.
When fire mode 2 is selected, the VFD runs
always, but the VFD stops when encountering
OUT1, OUT2, OUT3, OC1, OC2, OC3, OV1,
OV2, OV3, or SPO.
Note:
Terminal control must be used for a fire
mode.
0
◎
P28.26 Running frequency
in fire mode
0.00Hz–P00.03 (Max. output frequency)
50.00Hz
○
P28.27
Fire mode flag
0–1
When the fire mode has lasted 5 minutes, it
is reset, and no warranty of repair is
processed.
0
●
P28.28–
P28.29
Reserved
0–65535
0
○
P90 group––Customized function group 1
P90.00–
P90.39
Reserved
0–65535
0
○