GD350A series high-performance multifunction VFD
-204-
Function
code
Name
Description
Default Modify
Setting range:0x0000–0xFFFF
P10.36 PLC restart mode
0: Restart from the first step, namely if the VFD
stops during running (caused by stop
command, fault or power down), it will run from
the first step after restart.
1: Continue running from the step frequency
when interruption occurred, namely if the VFD
stops during running (caused by stop
command or fault), it will record the running
time of current step, and enters this step
automatically after restart, then continue
running at the frequency defined by this step
in the remaining time.
0
◎
P10.37 Multi-step time unit
0: second; the running time of each step is
counted in seconds;
1: minute; the running time of each step is
counted in minutes
0
◎
P11 group––Protection parameters
P11.00
Phase-loss
protection
0x000–0x111
Ones place:
0: Disable software input phase loss
protection
1: Enable software input phase loss protection
Tens place:
0: Disable output phase loss protection
1: Enable output phase loss protection
Hundreds place:
0: Disable hardware input phase loss
protection
1: Enable hardware input phase loss
protection
0x110
○
P11.01
Frequency drop at
transient power-off
0: Disable
1: Enable
0
○
P11.02
Energy braking for
stop
0: Enable
1: Disable
0
◎