GD350A series high-performance multifunction VFD
-110-
0
1
2
3
4
5
.
.
.
.
29
30
P06.01
P06.03
P06.04
P06.02
T delay
T delay
T delay
T delay
0
1
P06.05 output polarity
selection
(
Default value: 0
)
(
Default value: 0
)
(
Default value: 1
)
(
Default value: 5
)
P06.00
HDO
output type
0
1
0
1
0
1
delay
0
1
-1
-1
-1
-1
P17.12
Digital input
terminal state
P07.40
Digital output
terminal state
of current
fault
Fault
?
Fault
Run
Y
BIT0
HDO
BIT1
ROI
BIT2
RO2
BIT3
P06.05, P17.12, P07.40 display
P06.00
0: Open collector high-
speed pulse output
1: Open collector
output
P06.07
P06.09
P06.11
P06.13
Y
RO2
ROI
HDO
Digital switch-off delay
Digital output selection
T delay
T delay
T delay
T delay
delay
P06.06
P06.08
P06.10
P06.12
Digital switch-on delay
The following table lists the function code options. A same output terminal function can be repeatedly
selected.
Setting
Function
Description
0
Invalid
Output terminal has no function
1
In running
Output ON signal when there is frequency output
during running
2
In forward running
Output ON signal when there is frequency output
during forward running
3
In reverse running
Output ON signal when there is frequency output
during reverse running
4
In jogging
Output ON signal when there is frequency output
during jogging
5
VFD fault
Output ON signal when VFD fault occurred
6
Frequency level detection FDT1 Refer to P08.32 and P08.33.
7
Frequency level detection FDT2 Refer to P08.34 and P08.35.
8
Frequency reached
Refer to P08.36.
9
Running in zero speed
Output ON signal when the VFD output frequency
and reference frequency are both zero.
10
Reach upper limit frequency
Output ON signal when the running frequency
reaches upper limit frequency
11
Reach lower limit frequency
Output ON signal when the running frequency
reached lower limit frequency
12
Ready to run
Main circuit and control circuit powers are
established, the protection functions do not act;
when the VFD is ready to run, output ON signal.
13
In pre-exciting
Output ON signal during pre-exciting of the VFD
14
Overload pre-alarm
Output ON signal after the pre-alarm time