GD350A series high-performance multifunction VFD
-168-
Function
code
Name
Description
Default Modify
closed-loop output
limit in SM V/F
control
function code is used to set the output limit of
the reactive current closed-loop control. A
greater value indicates a higher reactive
closed-loop compensation voltage and higher
output power of the motor. In general, you do
not need to modify the function code.
Setting range: 0–16000
P04.40
Enabling IF mode
for AM 1
0: Disable
1: Enable
0
◎
P04.41
Current setting in IF
mode for AM 1
When IF control is adopted for AM 1, the
function code is used to set the output current.
The value is a percentage in relative to the
rated current of the motor.
Setting range: 0.0–200.0%
120.0%
○
P04.42
Proportional
coefficient in IF
mode for AM 1
When IF control is adopted for AM 1, the
function code is used to set the proportional
coefficient of the output current closed-loop
control.
Setting range: 0–5000
650
○
P04.43
Integral coefficient
in IF mode for AM 1
When IF control is adopted for AM 1, the
function code is used to set the integral
coefficient of the output current closed-loop
control.
Setting range: 0–5000
350
○
P04.44
Frequency
threshold for
switching off IF
mode for AM 1
0.00– P04.50
10.00Hz
○
P04.45
Enabling IF mode
for AM 2
0: Disable
1: Enable
0
◎
P04.46
Current setting in IF
mode for AM 2
When IF control is adopted for AM 2, the
function code is used to set the output current.
The value is a percentage in relative to the
rated current of the motor.
Setting range: 0.0–200.0%
120.0%
○
P04.47
Proportional
coefficient in IF
When IF control is adopted for AM 2, the
function code is used to set the proportional
650
○