Function
code
Name
Description
Default Modify
measurement
optimization
selection
1: Optimization mode 1
2: Optimization mode 2
P24.13
CD signal zero
offset gain
0–65535
0
○
P24.14
Encoder type
selection
Ones place: Incremental encoder
0: without UVW
1: with UVW
Tens place: Sin/Cos encoder
0: without CD signal
1: with CD signal
0x00
◎
P24.15
Speed
measurement mode
0: PG card
1: local; realized by HDIA and HDIB; supports
incremental 24V encoder only
0
◎
P24.16
Frequency division
coefficient
0–255
When the function code is set to 0 or 1,
frequency division of 1:1 is implemented.
0
○
P24.17
Pulse filter handling
selection
0x0000–0xFFFF
Bit0: Enable/disable encoder input filter
0: No filter
1: Filter
Bit1: Encoder signal filter mode (set Bit0 or
Bit2 to 1)
0: Self-adaptive filter
1: Use P24.18 filter parameters
Bit2: Enable/disable encoder frequency-
division output filter
0: No filter
1: Filter
Bit3: Reserved
Bit4: Enable/disable pulse reference filter
0: No filter
1: Filter
Bit5: Pulse reference filter mode (valid when
Bit4 is set to 1)
0: Self-adaptive filter
1: Use P24.19 filter parameters
Bit6: Frequency-divided output source setting
0x0033
○