GD350A series high-performance multifunction VFD
-216-
Function
code
Name
Description
Default Modify
When continuous communication is required,
you can set the function code to monitor
communication status.
P14.05
Transmission error
processing
0: Report an alarm and coast to stop
1: Keep running without reporting an alarm
2: Stop in enabled stop mode without reporting
an alarm (applicable only to communication
mode)
3: Stop in enabled stop mode without reporting
an alarm (applicable to any mode)
0
○
P14.06
Communication
processing action
0x00–0x11
Ones place:
0: Respond to write operations
1: Not respond to write operations
Tens place:
0: Password protection for communication is
invalid.
1: Password protection for communication is
valid.
0x00
○
P14.07 User-defined
running command
address
0x0000–0xFFFF
User-defined Modbus running command
address
0x2000
○
P14.08 User-defined
frequency setting
address
0x0000–0xFFFF
User-defined Modbus frequency setting
address
0x2001
○
P14.09 Modbus-TCP
communication
timeout time
0.0 (invalid)–60.0s
0.0s
○
P14.10–
P14.24
Reserved
0–65535
0
●
P15 group––Functions of communication expansion card
P15.00–
P15.27
See the communication expansion card operation manual.
P15.28 Master/slave CAN
communication
address
0–127
1
◎