GD350A series high-performance multifunction VFD
-10-
R
S
T
U
V
W
(
+
)
(
-
)
DC reactor
P1
PE
PE
Figure 3.4 Main circuit diagram for 132G/160P and higher models
Note:
132G/160P and higher models can be connected to external DC reactors. Before connection, take
off the copper bar between P1 and (+). 075G/090P and higher models can be connected to
external braking units. DC reactors and braking units are optional parts.
018G/022P–110G/132P models are equipped with built-in DC reactors.
037G/045P and lower models carry built-in braking units. Braking units are optional parts for
045G/055P–055G/075P models and they can be built in or externally connected to the models.
3.3 Product specifications
Function description
Specification
Power input
Input voltage (V)
AC 3PH 380V (-15%)–440V (+10%)
Input current (A)
See "Product ratings".
Input frequency (Hz) 50Hz
or 60Hz, allowable range: 47–63Hz
Power
output
Output voltage (V)
0–Input voltage
Output current (A)
See "Product ratings".
Output power (kW)
See "Product ratings".
Output frequency
(Hz)
0–400Hz
Technical
Control mode
Space voltage vector control, sensorless vector control