GD350A series high-performance multifunction VFD
-108-
Function
code
Name
Description
Default
38: Command switches to communication
39: Pre-exciting command
40: Zero out power consumption quantity
41: Maintain power consumption quantity
42: Source of upper torque limit switches to
keypad
56: Emergency stop
57: Motor over-temperature fault input
59: Switch to V/F control
60: Switch to FVC control
61: PID polarity switch-over
66: Zero out encoder counting
67: Pulse increase
68: Enable pulse superimposition
69: Pulse decrease
70: Electronic gear selection
71: Switch to the master
72: Switch to the slave
73: Trigger fire mode control
74–79: Reserved
Polarity of input terminal 0x00–0x3F
0x00
Digital filter time
0.000–1.000s
0.010s
Virtual terminal setting
0x00–0x3F (0: Disable; 1: Enable)
BIT0: S1 virtual terminal
BIT1: S2 virtual terminal
BIT2: S3 virtual terminal
BIT3: S4 virtual terminal
BIT4: HDIA virtual terminal
BIT8: HDIB virtual terminal
0x00
2/3-wire control mode
0: 2-wire control 1
1: 2-wire control 2
2: 3-wire control 1
3: 3-wire control 2
0
S1 terminal switch-on
delay
0.000–50.000s
0.000s
S1 terminal switch-off
delay
0.000–50.000s
0.000s