GD350A series high-performance multifunction VFD
-174-
Function
code
Name
Description
Default Modify
OFF
Run
forward
ON
ON
OFF→ON
Run
reversely
OFF
Run
reversely
ON→
OFF
Decelerate
to stop
Sin: Three-wire control; FWD: Forward
running; REV: Reverse running
Note:
For two-wire controlled running mode,
when the FWD/REV terminal is valid, if the
VFD stops due to a stop command given by
another source, the VFD does not run again
after the stop command disappears even if the
control terminal FWD/REV is still valid. To
make the VFD run, you need to trigger
FWD/REV again, for example, PLC single-
cycle stop, fixed-length stop, and valid
STOP/RST stop during terminal control. (See
P07.04.)
P05.12 S1 switch-on delay The function codes specify the delay time
corresponding to the electrical level changes
when the programmable input terminals
switch on or switch off.
Si Electrical
level
Si Valid
Invalid
Switch-off delay
Switch-on delay
Invalid
Valid
Setting range: 0.000–50.000s
Note:
After a virtual terminal is enabled, the
state of the terminal can be changed only in
communication mode. The communication
address is 0x200A.
0.000s
○
P05.13 S1 switch-off delay
0.000s
○
P05.14 S2 switch-on delay
0.000s
○
P05.15 S2 switch-off delay
0.000s
○
P05.16 S3 switch-on delay
0.000s
○
P05.17 S3 switch-off delay
0.000s
○
P05.18 S4 switch-on delay
0.000s
○
P05.19 S4 switch-off delay
0.000s
○