GD350A series high-performance multifunction VFD
-207-
Function
code
Name
Description
Default Modify
P11.10
Overload pre-alarm
detection time
overload pre-alarm signal will be outputted.
Y,
RO1, RO2
Output current
Overload pre-alarm
threshold
Time t
Time t
Pre-alarm time t
Pre-alarm time t
Setting range of P11.09: P11.11–200%
Setting range of P11.10: 0.1–3600.0s
1.0s
○
P11.11
Underload pre-
alarm detection
level
Underload pre-alarm signal will be outputted if
the output current of the VFD or motor is lower
than underload pre-alarm detection level
(P11.11), and the duration exceeds underload
pre-alarm detection time (P11.12).
Setting range of P11.11: 0–P11.09
Setting range of P11.12: 0.1–3600.0s
50%
○
P11.12
Underload pre-
alarm detection
time
1.0s
○
P11.13
Fault output
terminal action
upon fault occurring
The function code is used to set the action of
fault output terminals at undervoltage and fault
reset.
0x00–0x11
Ones place:
0: Act at undervoltage
1: Do not act at undervoltage
Tens place:
0: Act at fault reset
1: Do not act at fault reset
0x00
○
P11.14
Speed deviation
detection value
0.0–50.0%
Used to set the speed deviation detection
value.
10.0%
○