GD350A series high-performance multifunction VFD
-75-
Function
code
Name
Description
Default
Speed control
mode
0: Sensorless vector control (SVC) mode 0
1: Sensorless vector control (SVC) mode 1
2: Space voltage vector control mode
3: Closed-loop vector control mode
Note: To select 0, 1, or 3 as the control mode, enable
the VFD to perform motor parameter autotuning
first.
2
Enabling torque
control
0: Disable
1: Enable
0
Torque setting
method
1: Keypad (P03.12)
2: AI1 (100% corresponding to three times the
motor rated current)
3: AI2 (same as the above)
4: AI3 (same as the above)
5: Pulse frequency HDIA (same as the above)
6: Multi-step torque (same as the above)
7: Modbus/Modbus TCP communication (same as
the above)
8: Profibus/CANopen/DeviceNet communication
(same as the above)
9: Ethernet communication (same as the above)
10: Pulse frequency HDIB (same as the above)
11: EtherCat/Profinet/EtherNetIP communication
12: Programmable expansion card
Note:
For setting methods 2–12, 100% corresponds
to three times the motor rated current.
0
Torque set
through keypad
-300.0%–300.0% (of the motor rated current)
50.0%
Torque reference
filter time
0.000–10.000s
0.010s
Setting source of
forward rotation
upper-limit
frequency in
torque control
0: Keypad (P03.16)
1: AI1 (100% corresponding to the max. frequency)
2: AI2 (same as the above)
3: AI3 (same as the above)
4: Pulse frequency HDIA (same as the above)
5: Multi-step setting (same as the above)
6: Modbus/Modbus TCP communication (same as
the above)
0