GD350A series high-performance multifunction VFD
-148-
Function
code
Name
Description
Default Modify
Setting range: 0.0–3600.0s
P01.14
FWD/REV running
switching mode
0: Switch at zero frequency
1: Switch at the starting frequency
2: Switch after the speed reaches the stop
speed with a delay
0
◎
P01.15
Stop speed
0.00–100.00Hz
0.50Hz
◎
P01.16
Stop speed
detection mode
0: Detect by the set speed (unique in space
voltage vector control mode)
1: Detect by the feedback speed
0
◎
P01.17
Stop speed
detection time
0.00–100.00s
0.50s
◎
P01.18
Terminal-based
running command
protection at power-
on
When the channel of running commands is
terminal control, the system detects the state
of the running terminal during power-on.
0: The terminal running command is invalid at
power-on. Even the running command is
considered as valid during power-on, the
VFD does not run and it keeps the protection
state until the running command is canceled
and enabled again.
1: The terminal running command is valid at
power-on. If the running command is
considered as valid during power-on, the
VFD is started automatically after the
initialization.
Note:
Exercise caution before using this
function. Otherwise, serious result may
follow.
0
○
P01.19
Action selected
when running
frequency less than
frequency lower
limit (valid when
frequency lower
limit greater than 0)
The function code determines the running
state of the VFD when the set frequency is
lower than the lower-limit one.
0: Run at the frequency lower limit
1: Stop
2: Sleep
The VFD coasts to stop when the set
frequency is lower than the lower-limit one. If
the set frequency exceeds the lower limit one
0
◎