GD350A series high-performance multifunction VFD
-88-
Function
code
Name
Description
Default
direct start
Starting frequency hold
time
0.0–50.0s
0.0s
Braking current before
start
0.0–100.0%
0.0%
DC braking time before
start
0.00–50.00s
0.00s
ACC and DEC mode
0: Linear
1: S curve
Note:
If mode 1 is selected, set P01.06,
accordingly.
0
Stop mode
0: Decelerate to stop
1: Coast to stop
0
Starting frequency of DC
braking for stop
0.00Hz–P00.03 (Max. output frequency)
0.00Hz
Wait time before DC
braking for stop
0.00–50.00s
0.00s
DC braking current for
stop
0.0–100.0%
0.0%
DC braking time for stop 0.00–50.00s
0.00s
FWD/REV running
deadzone time
0.0–3600.0s
0.0s
FWD/REV running
switching mode
0: Switch at zero frequency
1: Switch at the starting frequency
2: Switch after the speed reaches the
stop speed with a delay
0
Stop speed
0.00–100.00Hz
0.50 Hz
Stop speed detection
mode
0: Detect by the set speed (unique in
space voltage vector control mode)
1: Detect by the feedback speed
1
Terminal-based running
command protection at
power-on
0: The terminal running command is
invalid at power-on
1: The terminal running command is
valid at power-on
0
Action selected when
running frequency less
0: Run at the frequency lower limit
1: Stop
0