GD350A series high-performance multifunction VFD
-150-
Function
code
Name
Description
Default Modify
P01.21=1)
P01.23
Start delay
After a VFD running command is given, the
VFD is in standby state and restarts with the
delay defined by P01.23 to implement brake
release.
Setting range: 0.0–600.0s
0.0s
○
P01.24 Stop speed delay 0.0–600.0s
0.0s
○
P01.25
Open-loop 0Hz
output selection
0: Output without voltage
1: Output with voltage
2: Output with the DC braking current for stop
0
○
P01.26
DEC time for
emergency stop
0.0–60.0s
2.0s
○
P01.27
Time of ending
segment of DEC S
curve
Time of starting
segment of DEC S
curve
0.0–50.0s
0.1s
◎
P01.28
Time of ending
segment of DEC S
curve
0.0–50.0s
0.1s
◎
P01.29
Short-circuit braking
current
When the VFD starts in direct start mode
(P01.00=0), set P01.30 to a non-zero value
to enter short-circuit braking.
During stop, if the running frequency of VFD
is lower than the starting frequency P01.09 of
brake for stop, set P01.31 to a non-zero
value to enter short-circuit braking for stop,
and then carry out DC braking in the time set
by P01.12. (Refer to the descriptions for
P01.09–P01.12.)
Setting range of P01.29: 0.0–100.0% (VFD)
Setting range of P01.30: 0.0–50.00s
Setting range of P01.31: 0.0–50.00s
0.0%
○
P01.30
Hold time of short-
circuit braking for
start
0.00s
○
P01.31
Hold time of short-
circuit braking for
stop
0.00s
○
P01.32
Pre-exciting time of
jog
0–10.000s
0.000s
○
P01.33 Starting frequency 0–P00.03
0.00Hz
○