GD350A series high-performance multifunction VFD
-300-
Function
code
Name
Description
Setting
range
Default
Modify
P00.03
Max. output
frequency
P00.04–600.00H
(400.00Hz)
100.00–
600.00
50.00Hz
◎
According to the number of decimals, the fieldbus scale of the "Max. output frequency" (P00.03) is
100. Multiply 100 Hz by 100. The value 10000 is obtained, and it is 2710H in the hexadecimal form.
The command transmitted by the master is as follows:
Parameter
address
VFD
address
Write
command
CRC
Parameter
data
03
06
00 03
27 10
62 14
If the operation is successful, the following response is returned (same as the command transmitted
by the master):
Parameter
address
VFD
address
Write
command
CRC
Parameter
data
03
06
00 03
27 10
62 14
Note:
In the preceding command description, spaces are added to a command just for explanatory
purposes. In practical applications, no space is required in the commands.
9.4.8.3 Examples of continuously write command 10H
Example 1: Set the VFD whose address is 01H to be forward running at the frequency of 10 Hz. Refer
to the table of other function parameters, the address of "Communication-based control command" is
2000H, 0001H indicates forward running, and the address of "Communication-based value setting" is
2001H, as shown in the following figure. 10 Hz is 03E8H in the hexadecimal form.
Function
Address
Data description
R/W
Communication-based
control command
2000H
0001H: Forward running
R/W
0002H: Reverse running
0003H: Forward jogging
0004H: Reverse jogging
0005H: Stop
0006H: Coast to stop (emergency stop)