GD350A series high-performance multifunction VFD
-260-
Fault
code
Fault type
Possible cause
Solution
in card slot 2
and confirm whether fault still
occurs at next power-on;
Check whether the insertion
port is damaged, if yes, replace
the insertion port after power
down
C3-Er
Communication
timeout
occurred to the
expansion card
in card slot 3
There is no data transmission in
interfaces of card slot 3
Confirm whether the expansion
card inserted can be supported;
Stabilize the expansion card
interfaces after power down,
and confirm whether fault still
occurs at next power-on;
Check whether the insertion
port is damaged, if yes, replace
the insertion port after power
down
E-DP
Profibus card
communication
timeout fault
There is no data transmission
between the communication card
and the host computer (or PLC)
Check whether the
communication card wiring is
loose or dropped
E-NET
Ethernet card
communication
timeout fault
There is no data transmission
between the communication card
and the host computer
Check whether the
communication card wiring is
loose or dropped
E-CAN
CANopen card
communication
timeout fault
There is no data transmission
between the communication card
and the host computer (or PLC)
Check whether the
communication card wiring is
loose or dropped
E-PN
Profinet card
communication
timeout fault
There is no data transmission
between the communication card
and the host computer (or PLC)
Check whether the
communication card wiring is
loose or dropped
E-CAT
EtherCat card
communication
timeout fault
There is no data transmission
between the communication card
and the host computer (or PLC)
Check whether the
communication card wiring is
loose or dropped
E-BAC
BACNet card
communication
timeout fault
There is no data transmission
between the communication card
and the host computer (or PLC)
Check whether the
communication card wiring is
loose or dropped
E-DEV
DeviceNET card
communication
timeout fault
There is no data transmission
between the communication card
and the host computer (or PLC)
Check whether the
communication card wiring is
loose or dropped