GD350A series high-performance multifunction VFD
-294-
Function
Address
Data description
R/W
Closed-loop setting
3008H -100.0–100.0% (Unit: 0.1%)
R
Closed-loop feedback 3009H -100.0–100.0% (Unit: 0.1%)
R
Input state
300AH
000–3F
Corresponding to the local HDIB/
HDIA/S4/S3/S2/S1
R
Output state
300BH
000–0F
Corresponding to the local
RO2/RO1/HDO/Y1
R
Analog input 1
300CH 0.00–10.00V (Unit: 0.01V)
R
Analog input 2
300DH 0.00–10.00V (Unit: 0.01V)
R
Analog input 3
300EH -10.00–10.00V (Unit: 0.01V)
R
Analog input 4
300FH
R
Read input of HDIA
high-speed pulse
3010H 0.00–50.00kHz (Unit: 0.01Hz)
R
Read input of HDIB
high-speed pulse
3011H
R
Read current step of
multi-step speed
3012H 0–15
R
External length
3013H 0–65535
R
External count value
3014H 0–65535
R
Torque setting
3015H -300.0–300.0% (Unit: 0.1%)
R
Identification code
3016H
R
Fault code
5000H
R
The Read/Write (R/W) characteristics indicate whether a function can be read and written. For example,
"Communication-based control command" can be written, and therefore the command code 6H is used
to control the VFD. The R characteristic indicates that a function can only be read, and W indicates
that a function can only be written.
Note:
Some parameters in the preceding table are valid only after they are enabled. Take the running
and stop operations as examples, you need to set "Running command channel" (P00.01) to
"Communication", and set "Communication running command channel" (P00.02) to the Modbus
communication channel. For another example, when modifying "PID setting", you need to set "PID