GD350A series high-performance multifunction VFD
-250-
Function
code
Name
Description
Default Modify
Setting range of P26.46: 0.00V–10.00V
Setting range of P26.47: 0.000s–10.000s
P26.48–
P26.52
Reserved
0–65535
0
○
P28 group––Master/slave control
P28.00 Master/slave mode
0: Master/slave control is invalid
1: The local machine is a master
2: The local machine is a slave
0
◎
P28.01
Master/slave
communication data
selection
0: CAN
1: Reserved
0
◎
P28.02
Master/slave
control mode
Ones place: Master/slave running mode
selection
0: Master/slave mode 0
(The master and slave adopt speed control
and maintain the power balance by droop
control)
1: Master/slave mode 1
(The master and slave must be in the same
type of vector control mode. The master is
speed control, and the slave will be forced to
be in the torque control mode.
2: Master/slave mode 2
Start in the slave first speed mode
(master/slave mode 0) and then switch to
torque mode at a certain frequency point
(master/slave mode 1)
Tens place: Slave start command source
selection
0: Follow the master to start
1: Determined by P00.01
Hundreds place: Slave transmitting/master
receiving data enable
0: Enable
1: Disable
0x001
◎
P28.03 Slave speed gain 0.0–500.0%
100.0%
○
P28.04 Slave torque gain 0.0–500.0%
100.0%
○