GD350A series high-performance multifunction VFD
-293-
Function
Address
Data description
R/W
0004H: Faulty
0005H: POFF
0006H: Pre-excited
VFD status word 2
2101H
Bit0: =0: Not ready to run =1: Ready to run
Bi1–2: =00: Motor 1 =01: Motor 2
Bit3: =0: Asynchronous motor =1: Synchronous
motor
Bit4: =0: No overload alarm =1: Overload alarm
Bit5–Bit6: =00: Keypad-based control =01:
Terminal-based control
=10: Communication-based control
Bit7: Reserved
Bit8: =0: Speed control =1: Torque control
Bit9: =0: Non position control
=1: Position control
Bit11–Bit10: =0: Vector 0 =1: Vector 1
=2: Closed-loop vector
=3: Space voltage vector
R
VFD fault code
2102H See the description of fault types.
R
VFD identification
code
2103H GD350A-----0x01A2
R
Running frequency
3000H 0–Fmax (Unit: 0.01Hz)
Compatible
with CHF100A
and CHV100
communication
addresses
R
Set frequency
3001H 0–Fmax (Unit: 0.01Hz)
R
Bus voltage
3002H 0.0–2000.0V (Unit: 0.1V)
R
Output voltage
3003H 0–1200V (Unit: 1V)
R
Output current
3004H 0.0–3000.0A (Unit: 0.1A)
R
Rotating speed
3005H 0–65535 (Unit: 1RPM)
R
Output power
3006H -300.0–300.0% (Unit: 0.1%)
R
Output torque
3007H -250.0–250.0% (Unit: 0.1%)
R