GD350A series high-performance multifunction VFD
-203-
Function
code
Name
Description
Default Modify
T3 OFF OFF OFF OFF ON ON ON ON
T4 ON ON ON ON ON ON ON ON
Step 8
9 10 11 12 13 14 15
P10.34
ACC/DEC time of
steps 0–7 of simple
PLC
The description is as follows (St indicates
step):
Code
Binary
St
ACC/
DEC
T1
ACC/
DEC
T 2
ACC/
DEC
T3
ACC/
DEC
T4
BIT1 BIT0 0 00 01 10 11
BIT3 BIT2 1 00 01 10 11
BIT5 BIT4 2 00 01 10 11
BIT7 BIT6 3 00 01 10 11
BIT9 BIT8 4 00 01 10 11
BIT11 BIT10 5 00 01 10 11
BIT13 BIT12 6 00 01 10 11
BIT15 BIT14 7 00 01 10 11
BIT1 BIT0 8 00 01 10 11
BIT3 BIT2 9 00 01 10 11
BIT5 BIT4 10 00 01 10 11
BIT7 BIT6 11 00 01 10 11
BIT9 BIT8 12 00 01 10 11
BIT11 BIT10 13 00 01 10 11
BIT13 BIT12 14 00 01 10 11
BIT15 BIT14 15 00 01 10 11
Select corresponding
acceleration/deceleration time, and then
convert 16-bit binary number into hexadecimal
number, finally, and then set corresponding
function codes.
ACC/DEC time 1 is set by P00.11 and P00.12;
ACC/DEC time 2 is set by P08.00 and P08.01;
ACC/DEC time 3 is set by P08.02 and P08.03;
Acceleration /deceleration time 4 is set by
0x0000
○
P10.35
ACC/DEC time of
steps 8–15 of
simple PLC
0x0000
○