GD350A series high-performance multifunction VFD
-192-
Function
code
Name
Description
Default Modify
Setting range of P08.34: 0.00Hz–P00.03
(Max. output frequency)
Setting range of P08.35: 0.0–100.0% (FDT2
electrical level)
P08.36
Detection value for
frequency being
reached
When the output frequency is within the
detection range, the multifunction digital
output terminal outputs the signal of
"Frequency reached".
Y,
RO1, RO2
Output frequency
Set
frequency
Detection amplitude
Time t
Time t
Setting range: 0.00Hz–P00.03 (Max. output
frequency)
0.00Hz
○
P08.37
Enabling energy
consumption
braking
0: Disable
1: Enable
1
○
P08.38
Energy
consumption
braking threshold
voltage
The function code is used to set the starting
bus voltage of energy consumption braking.
Adjust this value properly to achieve effective
braking for the load. The default value varies
depending on the voltage class.
Setting range: 200.0–2000.0V
For 220V:
380.0V;
For 380V:
700.0V;
For 660V:
1120.0V
○
P08.39
Cooling-fan running
mode
0: Normal mode
1: Permanent running after power-on
2: Running mode 2
0
○
P08.40
PWM selection
0x0000–0x1121
Ones place: PWM mode selection
0: PWM mode 1, 3PH modulation and 2PH
modulation
0x1101
◎