GD350A series high-performance multifunction VFD
-191-
Function
code
Name
Description
Default Modify
drop control
used to balance the power when several
motors drive a same load.
Setting range: 0.00–50.00Hz
P08.31
Channel for
switching between
motor 1 and motor
2
0x00–0x14
Ones place: Switchover channel
0: Terminal
1: Modbus/Modbus TCP communication
2: PROFIBUS/CANopen/DeviceNET
communication
3: Ethernet communication
4: EtherCat/Profinet/EtherNetIP
communication
Tens place: indicates whether to enable
switchover during running
0: Disable
1: Enable
0x00
◎
P08.32
FDT1 electrical
level detection
value
When the output frequency exceeds the
corresponding frequency of FDT electrical
level, the multifunction digital output terminal
continuously outputs the signal of "Frequency
level detection FDT". The signal is invalid only
when the output frequency decreases to a
value lower than the frequency corresponding
to (FDT electrical level—FDT lagging
detection value).
Time t
Output frequency f
FDT level
FDT lag
Y1,
RO1, RO2
Time t
Setting range of P08.32: 0.00Hz–P00.03
(Max. output frequency)
Setting range of P08.33: 0.0–100.0% (FDT1
electrical level)
50.00Hz
○
P08.33
FDT1 lagging
detection value
5.0%
○
P08.34
FDT2 electrical
level detection
value
50.00Hz
○
P08.35
FDT2 lagging
detection value
5.0%
○