GD350A series high-performance multifunction VFD
-59-
Function
code
Name
Description
Default
integral
coefficient I
Torque setting
method
11: Keypad (P03.12)
2: AI1 (100% corresponding to three times the motor
rated current)
3: AI2 (same as the above)
4: AI3 (same as the above)
5: Pulse frequency HDIA (same as the above)
6: Multi-step torque (same as the above)
7: Modbus/Modbus TCP communication (same as the
above)
8: Profibus/CANopen/DeviceNet communication
(same as the above)
9: Ethernet communication (same as the above)
10: Pulse frequency HDIB (same as the above)
11: EtherCat/Profinet/EtherNetIP communication
12: Programmable expansion card
Note: For setting methods 2–12, 100% corresponds to
three times the motor rated current.
1
Torque set
through
keypad
-300.0%–300.0% (of the motor rated current)
50.0%
Torque
reference filter
time
0.000–10.000s
0.010s
Setting source
of forward
rotation
upper-limit
frequency in
torque control
0: Keypad (P03.16)
1: AI1 (100% corresponding to the max. frequency)
2: AI2 (same as the above)
3: AI3 (same as the above)
4: Pulse frequency HDIA (same as the above)
5: Multi-step setting (same as the above)
6: Modbus/Modbus TCP communication (same as the
above)
7: Profibus/CANopen/DeviceNet communication
0