70
Adjustment
Room Controller KNX Touch One
• Status: 29.04.2014 • Errors excepted. Subject to technical changes.
Following a manual intervention, the affected drive or light remains in manual mode,
and automatic operations are switched off. Once the general Automatic Function time
point is reached, drives and light applications are once again set to Automatic. Alter-
natively, the automatic function can be set to reactivate following a manual interven-
tion. The period for this can be set.
The Automatic Reset prevents drives from being manually operated and then stay in
an unfavourable position (leaving windows accidentally open, or blinds retracted de-
spite the sunlight).
The general Automatic Reset and reset following a manual intervention can be sepa-
rately activated and de-activated in the Automatic functions menu for each drive group
and each unit.
General Automatic Reset:
Set the time point by selecting the hour and accordingly the minute fields and setting
the time using the arrow buttons. Default setting: 3:00 AM.
Automatic reset following a manual intervention:
Use the arrow keys to set the time interval after which Automatic functions should be
once again activated.Default setting: 60 minutes.
Confirm your setting with the
OK
button.
5.2.9.
TH sensor
If the measured values of the integrated sensors are affected by external influences,
they can be corrected manually. An external compound for temperature and humidity
can be set, too.
5.2.9.1. Setting the TH sensor using the ETS
Activate the
“
Transfer parameters” function for the TH sensor under
“
General
settings” in the ETS. Then set the indoor sensor in the appearing menu.
Making adjustments
Temperature and humidity deviations due to various malfunctions can be corrected in
the ETS:
Temperature offset (in 0.1 °C)
-70...70; 0
Humidity offset (in % absolute)
-20...20; 0
Automatic reset