115
Adjustment
Room Controller KNX Touch One
• Status: 29.04.2014 • Errors excepted. Subject to technical changes.
Preferences for
“
default applications”:
Heat control, second step (only for two-step heat control)
For 2-point control:
For PI control:
For possible settings, see Heat control, single-step
Cooling control
Value in %
(only if a set value is sent)
0 … 100
The control variable follows the rule upon triggering
Application
Maximum control variable
is reached at setpoint/
actual difference of
Reset time
Warm water heating
5 °C
150 min
floor heating
5 °C
240 min
Convection unit
4 °C
90 min
Electric heating
4 °C
100 min
Setpoint difference between
steps 1 and 2 in 0.1 °C
0...100; 40
Control type
• 2-point control
• PI control
Hysteresis in 0.1 °C
0 … 100; 20
Control variable is a
• 1-bit object
• 8-bit object
Value in %
(only when control variable is an 8-bit
object)
0 … 100
Upon shut-off, control variable should
(do not send: display 0%,
Send value: display shows value in %)
• not transmitted
• send a specific value
Value in %
(only if the control variable should send a
set value)
0 • 1
The control variable follows the rule upon triggering
Set control using
• Provided applications
• Controller parameter
Application
(only when the controller is set by means
of a
“
default application”)
• Cooling ceiling