Adjustment
Room Controller KNX Touch One
• Status: 29.04.2014 • Errors excepted. Subject to technical changes.
Object function „Input Extended/Brief“:
For the object function „Input Brief/Extended“, you can trigger the following com-
mands by variing the duration of the button press:
Button was pressed and
released before expiry of Time 1
==> Stop/Step
Maintained for longer than Time 1
==> Up/Down
Triggered between Times 1 and 1 + 2
==> Stop
Triggered after Times 1 + 2
==> No further stop
Object function „Display/Input 16/32-bit floating point“:
For object function "Display 16/32-bit floating point“ and „Input 16/32-bit floating
point", you can input the unit as text. Additionally, you can convert the value by using
the factors
a
(+/-, floating point) and
b
(number 1...65535).
Thus, the value of 10 m/s received from the bus could be displayed as 10 × (+0.1) × 36
= 36 km/h
5.6.2.
Universal menu at the screen
The Universal menu is used for display (e. g. measured values) and operation.
Universal menu, page 120
Function
Input Extended / Brief
Time 1 in 10 m/s
0...200; 40
Time 5.08 cm 10 m/s
0...24 000; 200
Function
• Display 16-bit floating point
• Display 32-bit floating point
• Input 16-bit floating point
• Input 32-bit floating point
Text for unit
Text input (max. 2 chars.)
Conversion factor a
-/+ 0,001 • ... • -/+ 10000
Conversion factor a
1 ... 65535
Up/down buttons