105
Adjustment
Room Controller KNX Touch One
• Status: 29.04.2014 • Errors excepted. Subject to technical changes.
Press the button to set the internal temperature to the desired cooling level (for the
night-time re-cooling). The button will only be activated once a night-time re-cooling
temperature has been set.
Use the arrow buttons to change the value as required.
Pre-setting: 16.0 °C .
Confirm your setting using the
OK
button.
Press the button to set the operating position for the night-time re-cooling. The button
will only be activated once a night-time re-cooling temperature has been set.
Input the operating position in % using the arrow buttons (0% = closed, 100% = fully
open). Pre-setting: 30%.
Confirm your setting using the
OK
button.
Press the button to set the ventilation running time. At the end of the ventilation period,
the normal automated ventilation is once again performed according to the tempera-
ture, air humidity and CO2 content.
Press
Select
to select the times. Activate one or more times on the list. These operat-
ing times can be individually customised.
Confirm your setting using the
OK
button.
To change any of the time periods set in the timer, press
Timer
.
Setting the timer at the screen, page 124
Press the button to set the outdoor temperature block. The effect of the block is that the
window remains in the current position. The outdoor temperature block can, for exam-
ple, be used if the window should not be used for ventilation in winter (cold protection
for plants).
The outdoor temperature block only applies for automatic operation; no ventilation
then takes place. When the rain or wind alarm is triggered, the window will be closed
despite the outdoor temperature block (the alarm has priority over temperature block).
Manual operation continues to remain possible, even when the window is blocked be-
cause of low outdoor temperatures.
NTC interior temp.
Only when night-time re-cooling has been activated
for this drive
NTC operation
Only when night-time re-cooling has been activated
for this drive
Timed ventilation
Outdoor temperature