104
Adjustment
Room Controller KNX Touch One
• Status: 29.04.2014 • Errors excepted. Subject to technical changes.
Press the button to set the interior temperature block (thermal protection). If no interior
room sensor is selected, the supply air temperature is not taken into consideration.
Activate: If the window should be closed when the supply air temperature is higher
than the room temperature, select
Yes
.
The supply air temperature-block becomes active as soon as the supply air tempera-
ture lies above the room temperature. The block is however only deactivated again
when the supply air temperature sinks more than 3.0 °C below the room temperature
(hysteresis).
Deactivate: If the window should be opened/remain open when the supply air temper-
ature is higher than the room temperature, select
No
(default setting).
Confirm your setting using the
OK
button.
Press the button to set the number of travel steps for a stepped window in automatic
operation. In stepped windows, the control system checks every 3 minutes whether the
set room temperature and/or air humidity is still undercut, and then if necessary ex-
tends this a further step.
Input the desired number of steps using the arrow buttons. Pre-setting: 5.
Confirm your setting using the
OK
button.
Press the button to set the times for night-time re-cooling. The button is only active
when the general settings for the night-time re-cooling have already been input and
the TH sensor for the window has been selected.
Settings > Automatic > Night-time re-cooling
Change automatic settings at the screen, page 67
Press
Select
to select the times during which the night-time re-cooling should be ac-
tivated. Activate one or more times on the list.
Confirm your setting by pressing the
OK
button.
To change any of the time periods set in the timer, press
Timer
.
Setting the timer at the screen, page 124
Be careful that your timer settings do not prevent night-time re-cooling operations!
Supply air
only when an indoor sensor is selected
Number of steps
Only for step windows.
Only when an indoor sensor is selected
Night-time cooling
Only if night-time re-cooling is activated.
Only when an indoor sensor is selected