![Elsner KNX Touch One Installation And Operation Manual Download Page 9](http://html1.mh-extra.com/html/elsner/knx-touch-one/knx-touch-one_installation-and-operation-manual_2396577009.webp)
8
Description
Room Controller KNX Touch One
• Status: 29.04.2014 • Errors excepted. Subject to technical changes.
Concerning the
accuracy
of the measurement, please not chapter
Installation location
The product conforms with the provisions of EC guidelines
•
EMC Directive 2004/108/EC
•
Low Voltage Directive 2006/95/EC
•
R&TTE Directive 1999/5/EG
The following standards and/or technical specifications have been applied:
•
EN 301489-1 V1.9.2
•
EN 300220-2 V2.1.2
•
EN 50491-5-1 : 2010
•
EN 50491-5-2 : 2011
1.1.2.1. Automatic intrinsic heat balancing by TH sensor
To ensure exact temperature displays, the temperature measurement takes into con-
sideration the unit's intrinsic heat. For wall mounting at a height of 1.50 m, an average
temperature variation due to intrinsic heat is determined to be 1.6°C.
The software compensates for temperature variations automatically by reducing the
actually measured temperature by the intrinsic heat of 1.6°C and displaying this.
During the 90-minute warm-up phase, the displayed interior temperature measure-
ment value increasingly approaches the actual room temperature.
1.2.
Maintenance and care
Finger marks on the touch screen are best removed with a damp cloth or a microfiber
cloth. You can wipe the buttons without activating them.
Do not use abrasives / detergents or aggressive cleaners for cleaning.
If there is a power outage, the data you have entered will be saved for around 10 years.
No battery is required for this.
1.3.
Connection and control options
The following
ambient parameters
are measured and displayed:
•
Indoor temperature
•
Air humidity, interior
The following
ambient parameters
must be received:
•
Brightness
•
Wind speed
•
Precipitation
•
Outdoor temperature
This data can be provided by Suntracer KNX, Suntracer KNX-GPS, or Suntracer KNX-
GPS light weather sensors.