116
Adjustment
Room Controller KNX Touch One
• Status: 29.04.2014 • Errors excepted. Subject to technical changes.
Preferences for
“
default applications”:
Cooling control, second step (only shown for two-step cooling control)
For 2-point control:
For PI control:
For possible settings, see Cooling control, first step
Night-time reduction:
Maximum control variable is reached
at setpoint/actual difference of in °C
(only when controller is set by means of
“
controller parameter”)
1 ... 5
Reset time in min
(only when controller is set by means of
“
controller parameter”)
1 … 255; 30
Upon shut-off, control variable should
• not transmitted
• send a specific value
Value in %
(only if a set value is sent)
0 … 100
The control variable follows the rule upon triggering
Application
Maximum control variable
is reached at setpoint/
actual difference of
Reset time
Cooling ceiling
5 °C
240 min
Setpoint difference between
steps 1 and 2 in 0.1 °C
0...100; 40
Control type
• 2-point control
• PI control
Hysteresis in 0.1 °C
0 … 100; 20
Control variable is a
• 1-bit object
• 8-bit object
Value in %
(only when control variable is an 8-bit
object)
0 … 100
Upon shut-off, control variable should
(do not send: display 0%,
Send value: display shows value in %)
• not transmitted
• send a specific value
Value in %
(only if the control variable should send a
set value)
0 ...100
The control variable follows the rule upon triggering
Use night-time reduction
No • Yes