107
Adjustment
Room Controller KNX Touch One
• Status: 29.04.2014 • Errors excepted. Subject to technical changes.
Press the button to set the wind alarm. The wind alarm protects the device and equip-
ment from damage by closing the window. Even manually opened windows are closed
in the event of a wind alarm.
Adjust values: Adjust the values for wind speed (default setting: 6 m/s) and the dura-
tion that this is exceeded (default setting: 1 sec.) using the arrow buttons.
Deactivate:If the window need not react to the wind, select
Do not close
(default set-
ting).
Confirm your setting using the
OK
button.
A wind alarm actuated for the drive will remain active for 5 minutes. If the saved value
is exceeded in these 5 minutes, the stoppage time will be restarted.
Press the button to switch the rain alarm on or off. The rain alarm provides protection
from humidity damage by sending the security object. Even manually opened win-
dows are closed in the event of a rain alarm.
Activate: If the security object should be sent, select
Yes
.
Deactivate: If the security object should not be sent in the event of rain, select
No
(de-
fault setting).
Confirm your setting using the
OK
button.
A certain amount of time may pass before precipitation is
recognised by the weather equipment, depending on the rain
amount and temperature. The operating time taken to close the
window must also be included in this calculation. Humidity-sensitive
items should not be placed within range of the automatic windows.
Press the button to switch gap openings in the event of a rain alarm on or off. This func-
tion is only active when the rain alarm has been switched on. Gap opening allows the
window to be opened slightly despite a rain alarm.
Activate: If gap opening should be activated when it is raining, select
Yes
.
Deactivate: If the window should be fully closed in the event of rain, select
No
(default
setting).
Confirm your setting using the
OK
button.
Wind alarm
Rain alarm
Gap ventilation