![Elsner KNX Touch One Installation And Operation Manual Download Page 91](http://html1.mh-extra.com/html/elsner/knx-touch-one/knx-touch-one_installation-and-operation-manual_2396577091.webp)
90
Adjustment
Room Controller KNX Touch One
• Status: 29.04.2014 • Errors excepted. Subject to technical changes.
Change general automatic settings using the ETS, page 66
When the TH sensor is used:
Use timed ventilation for
Period 1 - 16
No
• Yes
Use external temperature shut-off
No
• Yes
Close when below (in 0.1 °C)
(only if an exterior temperature lock is
used)
-100...200; 50
Use timed closure for
Period 1 - 16
No
• Yes
Use frost protection
No
• Yes
Use wind alarm
No
• Yes
Retract at wind speeds from (in 0.1 m/s)
(only if wind alarm is used)
5...195; 60
for longer than (in sec)
(only if wind alarm is used)
1...5
Close during rain
No
• Yes
Use gap opening during rain
(only when the window closes due to rain)
No
• Yes
Gap opening (in %)
(only if gap-opening due to rain is used)
0...100; 5
Perform Automatic Reset
at set time
No
• Yes
after the input waiting period following
manual operation
No
• Yes
Use TH sensor
Yes
Use interior temperature
No
•
Yes
Open from (in 0.1 °C)
(only if the interior temperature is used)
50...500; 250
Use air humidity
No
• Yes
Open from (in % rH)
(only if the air humidity is used)
10...95; 80
Use CO2
No
• Yes
Open from above (in 10 ppm)
(only if the CO2 content is used)
50...200; 80
Close from below (in 10 ppm)
(only if the CO2 content is used)
50...200; 55
Close the window when the supply air
temp. is higher than the room temperature
No
• Yes
Use night-time cooling for
Period 1 - 16
No
• Yes