Adjustment
Room Controller KNX Touch One
• Status: 29.04.2014 • Errors excepted. Subject to technical changes.
Heating control
Storage of the last received value
• not
• After reset
• After reset and programming
(Attention: Do not use during initial
start-up)
Heating initial setpoint (in 0.1 °C)
valid till 1st communication
-300 … 800; 220
H min. object value limit (in 0.1 °C)
(restricts the input of the reference
temperature on the touch display
appropriately)
-300 … 800; 140
Object value limit Hmax (in 0.1 °C)
(restricts the input of the reference
temperature on the touch display
appropriately)
-300 … 800;
250
Cooling initial setpoint (in 0.1 °C)
valid till 1st communication
-300 … 800; 260
K min. object value limit (in 0.1 °C)
(restricts the input of the reference
temperature on the touch display
appropriately)
-300 … 800; 140
K max. object value limit (in 0.1 °C)
(restricts the input of the reference
temperature on the touch display
appropriately)
-300 … 800; 300
Type of setpoint change
• Absolute value
• Increase / Decrease
Increment (in 0.1 °C)
(only when
“
increase/reduce” is used)
1 … 50;
10
Set control using
• Controller parameter
• provided applications
Application
(only when the controller is set by means
of a
“
default application”)
• Warm water heating
• Floor heating
• Convection unit
• Electric heating
Maximum control variable is reached
at setpoint/actual difference of (in °C)
(only when controller is set by means of
“
controller parameter”)
1 ... 5
Reset time (in min)
(only when controller is set by means of
“
controller parameter”)
1 … 255; 30
Upon shut-off, control variable should
• not transmitted
• send a specific value