Adjustment
Room Controller KNX Touch One
• Status: 29.04.2014 • Errors excepted. Subject to technical changes.
5.2.1.
Basic setting in the ETS
General, monitoring wind/rain:
The monitoring of the wind and rain object is active and set to “every 5 seconds“ by
default
You must ensure that the unit can receive weather data at the
selected monitoring interval (e.g. every 5 seconds) when wind
and rain object monitoring is activated.
Transfer/set general parameters:
When a parameter is set to “Yes“, it appears in the menu on the left. Settings can be
made there.
If you transfer parameters, the settings which have been made
manually on the screen will be overwritten.
The setting options of the parameters are discribed in the chapters
Language, Date and
time
...
Maximum message rate
1 • 2 • 5 • 10 • 20 messages per second
Transmission delays after power-up and
programming
5 s … 2 h
Using wind and rain object monitoring
No • Yes
Monitoring period
(only if monitoring is used)
5 s … 2 h
Transfer the following parameters:
(Attention: If you transfer these parameters, the settings which have been
made manually on the touch display will be overwritten.)
Language
No • Yes
Date and time
No • Yes
Location
No • Yes
Display
No • Yes
Automatically transfer all
No • Yes
TH sensor
No • Yes
Alarm
No • Yes
Access code
No • Yes