Troubleshooting by Error Code
SiUS342303E
235
Part 6 Service Diagnosis
Note(s)
1. The system can keep operating, however, be sure to check and repair.
2. The system may or may not continue operation depending on the conditions.
3. Regarding the error codes and descriptions of the low-temperature hydrobox (HXY-TA), refer to
the service manual SiUS392016EA.
Outdoor
Unit
J3
l
Discharge pipe thermistor abnormality
Compressor body thermistor abnormality
J5
l
Suction pipe before accumulator thermistor abnormality
J6
l
Heat exchanger deicer thermistor abnormality
Heat exchanger gas pipe thermistor abnormality
J7
l
Subcooling liquid pipe thermistor abnormality
Subcooling injection thermistor abnormality
J8
l
Heat exchanger liquid pipe thermistor abnormality
J9
l
Subcooling gas pipe thermistor abnormality
Electrical box air outlet thermistor abnormality
JA
l
High pressure sensor abnormality
JC
l
Low pressure sensor abnormality
L1
l
Inverter PCB abnormality
L4
l
Inverter radiation fin temperature rise abnormality
L5
l
Compressor instantaneous overcurrent
L8
l
Compressor overcurrent
L9
l
Compressor startup abnormality
LC
l
Transmission error between inverter PCB and outdoor unit main PCB
P1
l
Power supply voltage imbalance
P4 (
1)
l
Inverter radiation fin temperature abnormality
PJ
l
Field setting abnormality after replacing outdoor unit main PCB or combination of
PCB abnormality
System
U0 (
1)
k
Refrigerant shortage
U1
l
Reverse phase, Open phase, Power supply frequency issue
U2
l
Power supply insufficient or instantaneous abnormality
U3
l
Check operation not executed
U4
l
Transmission error between indoor units and outdoor units, open phase in power
supply wiring
U5
l
Transmission error between remote controller and indoor unit
U7
l
Transmission error between outdoor units
U8
l
Transmission error between main and sub remote controllers
U9
l
Transmission error between indoor units and outdoor units in the same system
UA
l
Improper combination of indoor unit and outdoor unit
Incorrect gas furnace connecting number
Incorrect electric heater capacity setting
UC (
1)
k
Address duplication of centralized controller
UE
l
Transmission error between centralized controller and indoor unit
UF
l
System not set yet
UH
l
System abnormality, refrigerant system address undefined
Climate Talk communication system combination error (before initial setting for
communication completes)
Climate Talk communication system combination error (after initial setting for
communication completes)
Error
code
Operation
lamp
Error contents
Reference
page
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...