Troubleshooting by Error Code
SiUS342303E
353
Part 6 Service Diagnosis
YES
NO
The
multi transmission
wirings to multi Sub unit
have caused wiring disconnection
in them or are being
disconnected.
Modify the outdoor unit multi
transmission wirings, and then
reset the power supply.
Replace the outdoor unit main
PCB (A1P) for multi Sub unit.
Diagnosis Flowchart-3
(Transmission error between Master
and Sub units)
Error code
Sub code
U7-03
Disconnect the outdoor unit multi
transmission wirings, and then
reset the power supply.
Replace the outdoor unit main
PCB (A1P).
YES
NO
Diagnosis Flowchart-4
(Multi system error)
Error code
Sub code
U7-05
Multi outdoor unit
system?
YES
NO
Modify the outdoor unit multi
transmission wirings, and then
reset the power supply.
Replace the outdoor unit main
PCB (A1P).
One of
outdoor unit
multi transmission wirings has
caused wiring disconnection in it
or been disconnected.
Diagnosis Flowchart-5
(Manual address setting error for Sub
unit)
Error code
Sub code
U7-06
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...