3. Standby Control
3.1 Restart
Standby
Used to forcedly stop the compressor for a period of 2 minutes, in order to prevent the frequent
ON/OFF of the compressor and equalize the pressure within the refrigerant system.
In addition, the outdoor fan carry out the residual operation for a while to accelerate pressure
equalizing and to suppress migration of the refrigerant to the evaporator.
3.2 Crankcase
Heater
Control
In order to prevent the refrigerant from migrating into the compressor oil while not operating,
outdoor air temperature, compressor body temperature, etc., are used to control the crankcase
heater.