Troubleshooting by Error Code
SiUS342303E
273
Part 6 Service Diagnosis
Note(s)
1. Connector
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
Properly connect the
connector.
Is the connector
(
1) on the indoor unit control
PCB properly connected?
NO
NO
Normal.
The error could be caused by
other causes. Refer to other
diagnosis flowcharts in the
following order:
AH-05
→
04
→
06
→
07
→
08
→
09.
Check the indoor unit control
PCB and self-cleaning
decoration panel PCB.
AH-03
Transmission error between
self-cleaning decoration panel
and indoor unit
Diagnosis Flowchart-1
NO
Properly connect the
connector.
Is the
connector X1A on the
self-cleaning decoration panel PCB
properly connected?
YES
NO
Properly connect the
connector.
Is the relay
connector between
connector (
1) of indoor unit and
X1A of self-cleaning decoration
panel properly
connected?
YES
YES
Replace the harness.
Is the harness broken?
YES
YES
Remove the external factor.
Is there any
external factor other than the
error such as noise?
NO
Turn OFF the power supply and
then turn it ON again. Then, start
operation with remote controller.
Error
AH
recurs,
or the self-cleaning decoration panel
lamp (red) blinks?
Model
Connector
FXFQ-T
X8A
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...