Troubleshooting by Error Code
SiUS342303E
337
Part 6 Service Diagnosis
3.56 Inverter Radiation Fin Temperature Abnormality
3.56.1 Inverter Radiation Fin Temperature Abnormality (Inverter PCB)
Applicable
Models
All outdoor unit models
Error Code
P4
Sub code: 09-13
Method of Error
Detection
Detect the resistance of the following thermistors while the compressor is not running:
Radiation fin thermistor
Thermistor located in PCB circuit
Heat sink thermistor
Error Decision
Conditions
When the resistance of the thermistor comes to a value equivalent to open or short circuit.
Error is not decided while the unit operation is continued.
P4
will be displayed by pressing the inspection button.
Supposed
Causes
Defective radiation fin temperature thermistor
Defective inverter PCB
Defective compressor
Defective fan motor
Troubleshooting
Make measurement of
resistance of the radiation fin
thermistor.
Is the
resistance of the
relevant thermistor
normal?
The
insulation
resistance of the
relevant compressor is not
more than 100 k
.
The insulation
resistance of the relevant
fan motor is not more
than 1 M
.
Turn ON
the power supply.
Does the error
recur?
NO
YES
NO
YES
NO
YES
YES
NO
Replace the inverter PCB.
Replace the compressor.
Replace the fan motor
(M1F, M2F).
Replace the inverter PCB.
Continue operation.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...