SiUS342303E
Troubleshooting by Error Code
Part 6 Service Diagnosis
288
3.25 Combination Error between Indoor Unit Control PCB and
Fan PCB
Applicable
Models
FXSQ-TB, FXMQ-PB, FXMQ-TB
Error Code
C6
Method of Error
Detection
Check the condition of transmission with fan PCB (A2P) using indoor unit control PCB (A1P).
Error Decision
Conditions
When the communication data of fan PCB (A2P) is determined as incorrect.
Supposed
Causes
Defective fan PCB (A2P)
Defective connection of capacity setting adaptor
Field setting error
Troubleshooting
N
O
Caution
Be sure to turn off the po
w
er s
w
itch before connecting or disconnecting
connectors, or parts may be damaged.
W
as
indoor unit
control PCB
(A1P) replaced
w
ith a spare
PCB?
YES
YES
YES
N
O
N
O
W
as
correct
capacity setting
adaptor installed
w
hen replacing it
w
ith a spare
PCB?
After establishing transmission
for indoor and outdoor units,
diagnose the operation again.
After establishing transmission
for indoor and outdoor units,
diagnose the operation again.
Replace it
w
ith correct fan PCB
(A2P).
Install correct capacity setting
adaptor.
Does
the fan PCB
part
N
o. match that
of the spare
parts list?
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...