Troubleshooting by Error Code
SiUS342303E
291
Part 6 Service Diagnosis
Note(s)
Reference
3.28 Remote Sensor Abnormality
Applicable
Models
FXTQ-TA, CXTQ-TA
Error Code
C9
Method of Error
Detection
The error is detected by remote sensor temperature.
Error Decision
Conditions
When the remote sensor becomes disconnected or shorted while the unit is running.
Supposed
Causes
Defective indoor unit thermistor (R1T) for room temperature
Defective indoor unit PCB
Troubleshooting
1. Connector and indoor unit control PCB
CHECK 11
Refer to page 381.
Is the
optional remote sensor
is installed?
Field setting
10(20)-2 is set to
03
.
Connector is
connected to the indoor
unit control PCB
(
1).
Resistance
is normal when
measured after
disconnecting the sensor
from the indoor unit
control PCB.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Set to
03
.
Replace the indoor unit control
PCB.
NO
NO
YES
YES
Replace the indoor unit control
PCB.
Connect the sensor and turn ON
again.
NO
NO
Replace the sensor (R1T).
YES
YES
CHECK 11
Connector for remote sensor
PCB
X4A
A1P
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...