[2-81]:
Cooling comfort setting
Default value: 1
Value
[2-81]
Cooling comfort setting
0
Eco
1 (default)
Mild
2
Quick
3
Powerful
Change [2-81] to 0, 1, 2 or 3 in function of required limitation.
This setting is used in conjunction with setting [2-8].
For more information and advice about the effect of these settings, refer to
Energy Saving and
Optimum Operation
[2-82]:
Heating comfort setting
Default value: 1.
Value
[2-82]
Heating comfort setting
0
Eco
1 (default)
Mild
2
Quick
3
Powerful
Change [2-82] to 0, 1, 2 or 3 in function of required limitation.
This setting is used in conjunction with setting [2-9].
For more information and advice about the effect of these settings, refer to
Energy Saving and
Optimum Operation
[2-83]:
Master user interface allocation in case
VRV
indoor units and Mini-split indoor units
are used at the same time
By changing setting [2-83], you can allow the
VRV
indoor unit to be the operation
mode selector (system power OFF/ON is required after applying this setting).
Default value: 1
Value
[2-83]
Master user interface allocation
0
VRV
indoor unit has mode selection right
1 (default)
Mini-split indoor unit has mode selection right
[2-87]:
Intermittent fan operation
Outdoor fan speed would be increased for assisting to discharge snow on outdoor
fan when outdoor fan is stop or low speed.
Default value: 0.
Value
[2-87]
Intermittent fan operation
0 (default)
OFF
1
30 minutes OFF, 1 minute ON with medium fan speed
2
30 minutes OFF, 1 minute ON with high fan speed
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...