Protection Control
SiUS342303E
111
Part 4 Functions and Control
6. Protection Control
6.1 High Pressure Protection Control
This high pressure protection control is used to prevent the activation of protection devices due to
abnormal increase of high pressure and to protect compressors against the transient increase of
high pressure.
Cooling
The following control is performed in the entire system.
Heating
The following control is performed in the entire system.
Normal control
High pressure standby
Reduce compressor capacity step
When occurring 3 times within 40
minutes, high pressure switch is
activated without high pressure standby,
thus outputting the error code
E3
.
Pc: High pressure sensor detection
value for each outdoor unit.
Pc > 3.55 MPa
(515 psi)
Pc < 3.04 MPa
(441 psi)
Pc > 3.72 MPa
(540 psi)
Normal control
High pressure standby
Reduce compressor capacity step
When occurring 3 times within 40
minutes, high pressure switch is
activated without high pressure standby,
thus outputting the error code
E3
.
Pc > 3.04 MPa
(441 psi)
Pc < 2.89 MPa
(419 psi)
Pc > 3.72 MPa
(540 psi)
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...