Troubleshooting by Error Code
SiUS342303E
367
Part 6 Service Diagnosis
3.73 System Abnormality, Refrigerant System Address
Undefined
Applicable
Models
All indoor unit models
All outdoor unit models
Error Code
UH
Method of Error
Detection
System detects an indoor unit whose address is not defined by automatic address function.
*Automatic address refers to the automatic designated address of indoor unit and outdoor unit
when connected to the power after installation or wiring replacement (with the
RETURN (BS3)
button pressed for more than 5 seconds).
Error Decision
Conditions
The error decision is made as soon as the abnormality aforementioned is detected.
Supposed
Causes
Improper connection of transmission wiring between indoor-outdoor units and outdoor-outdoor
units
Defective indoor unit PCB
Defective outdoor unit main PCB (A1P)