Troubleshooting by Error Code
SiUS342303E
315
Part 6 Service Diagnosis
Troubleshooting
Connect the Service Checker.
Mount a pressure gauge on the high pressure
service port.
Reset the operation, and then restart the operation.
Stop the relevant indoor units while the system
is in cooling operation, and then check for the
liquid pipe temperature of these indoor units
after the system is stabilized.
The liquid
pipe temperature is
low (equivalent to the
evaporating
temperature).
Clean the air filters
of the indoor units.
NO
YES
NO
Replace the indoor
unit electronic
expansion valve.
Replace the relevant
thermistor.
YES
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Are the
characteristics of
the suction pipe
thermistor and the
compressor suction
thermistor normal?
NO
Replace the discharge
pipe thermistor.
YES
NO
Replace the high
pressure sensor
(S1NPH).
Are the high
pressure sensor
characteristics
normal?
Are the
discharge pipe
thermistor characteristics
normal?
Service Checker
Use the Service Checker to find indoor units operating under the following conditions:
&
• Gas pipe temperature – Liquid pipe temperature < 2.5°C (4.5°F)
• Electronic expansion valve opening < 300 pulses
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...