SiUS342303E
Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
208
When heat pump lockout mode has been set the auto backup function will automatically be set.
This will allow the auxiliary or secondary heat source to be automatically energized in the event of a
system failure.
Error codes capable of auto backup are listed in the table below.
Please be aware that the error codes that are not listed do not auto backup in order to protect the
unit.
[2-47]: Heat pump lockout release differential
Heat pump would be resumed when the outdoor air temperature is recovered by differential
(below) above the heat pump lockout temperature.
Heat pump lockout
release differential
Fahrenheit (°F)
Celsius (°C)
0
5
2.8
1 (default)
10
5.6
2
15
8.3
Error contents
Error code
(Auto backup possible)
Activation of high pressure switch
E3
Activation of low pressure sensor
E4
Compressor motor lock
E5
Compressor damage alarm
E6
Outdoor fan motor abnormality
E7
Electronic expansion valve coil abnormality
E9
Position signal abnormality of outdoor unit fan motor
H3
H7
Outdoor air thermistor abnormality
H9
Discharge pipe temperature abnormality
F3
Wet alarm
F4
Discharge pipe thermistor abnormality
Compressor body thermistor abnormality
J3
Suction pipe thermistor abnormality
J5
Heat exchanger deicer thermistor abnormality
Heat exchanger gas pipe thermistor abnormality
J6
Subcooling heat exchanger liquid pipe thermistor abnormality
J7
Heat exchanger liquid pipe thermistor abnormality
J8
Subcooling heat exchanger gas pipe thermistor abnormality
Electrical box air outlet thermistor abnormality
J9
High pressure sensor abnormality
JA
Low pressure sensor abnormality
JC
Inverter PCB abnormality
L1
Radiation fin temperature rise abnormality
L4
Compressor instantaneous overcurrent
L5
Compressor overcurrent
L8
Compressor startup abnormality
L9
Transmission error between inverter and outdoor unit main PCB
LC
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...