Field Setting from Outdoor Unit
SiUS342303E
203
Part 5 Field Settings and Test Operation
Note(s)
This setting may result in a longer reaction time to large load variations.
[2-39]:
Emergency operation “Sub”
To disable compressor operation of “Sub” unit of a multi outdoor system permanently:
Default value: 0. Compressor operation enabled.
Field setting:
Set 1: Sub INV. 1 is disabled permanently.
Set 2: Sub INV. 2 is disabled permanently
Set 3: Sub module is disabled permanently.
[2-42]:
Outdoor fan noise countermeasure
Change fans rotational speed and reduce noise by the interference of air blow noise
between outdoor units.
Default value: 0
Field setting:
Mode A: 1
Mode B: 2
[2-49]:
Height difference setting
Default value: 0.
In case the outdoor unit is installed in the highest position (indoor units are installed
on a lower position than outdoor units) and the height difference between the lowest
indoor unit and the outdoor unit exceeds 50 m (164 ft), the setting [2-49] has to be
changed to 1.
[2-51]:
Master/Sub setting Multi
When 2 modules are installed as a multi-outdoor (by common refrigerant piping and
wiring by terminals Q1Q2) configuration is automatically detected. In certain cases, the
sequence of the Sub unit need to be set manually (in case of AIRNET monitoring).
Default value: 0. Automatic detection.
Field setting: ensure that the modules in a multi are set different status. Even some
modules in a multi are set manually to same status, U7 error will appear.
1: forced “Master” (F1F2/Ind terminals should be connected to indoor units).
2: forced “Sub” (only Q1Q2 terminals should be wired to “Master” module).
[2-62]:
Cooling and heating capacity learning control
Default value: 0.
Value
[2-62]
Description
0 (default)
OFF
1
Cooling adjustment
2
Heating adjustment
3
Cooling and heating adjustment
Adjust cooling and heating system operation to achieve stable capacity.
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...