Troubleshooting with Remote Controller
SiUS342303E
233
Part 6 Service Diagnosis
The upper digit of the code changes as shown below.
Continuous beep :
Both upper and lower digits match. (Error code is confirmed.)
2 short beeps :
The upper digit matches but the lower digit does not.
1 short beep :
The upper digit does not match.
5. Press
MODE
button. The right
0
(lower digit) indication of the error code blinks.
6. Press
UP
button or
DOWN
button and change the error code lower digit until the receiver of the
indoor unit generates a continuous beep.
The lower digit of the code changes as shown below.
Continuous beep :
Both upper and lower digits match. (Error code is confirmed.)
2 short beeps :
The upper digit matches but the lower digit does not.
1 short beep :
The upper digit does not match.
7. Press
MODE
button to return to the normal mode. If you do not press any button for 1 minute,
the remote controller automatically returns to the normal mode.
O0 A C E H F J L P U 9 8 7 6 5 4
"UP" button "DOWN" button
0 1 2 3 4 5 6 7 8 9 A H C J E F
"UP" button "DOWN" button
If no button is pressed
for 1 minute, equipment
returns to normal mode.
3. Press
MODE
button.
The upper digit
blinks.
Normal mode
1. Press
INSPECTION/TEST
button to enter
inspection mode.
7. When
MODE
button is
pressed or no button is
pressed for 1 minute,
equipment returns to
normal mode.
6. Change the lower
digit with
UP
button or
DOWN
button.
If no button is pressed
for 1 minute, equipment
returns to normal mode.
5. Press
MODE
button.
The lower digit blinks.
4. Change the
upper digit with
UP
button or
DOWN
button.
2. Change the unit number with
UP
button or
DOWN
button.
If no button is pressed
for 1 minute, equipment
returns to normal mode.
3. Pres
butto
The
blink
1. Press
INSPECTION/TEST
button to enter
inspection mode.
7. When
MODE
button is
pressed or no button is
pressed for 1 minute,
equipment returns to
normal mode.
r
If no button is pressed
for 1 minute, equipment
returns to normal mode.
5. Press
MODE
button.
The lower digit blinks.
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...