SiUS342303E
Troubleshooting by Error Code
Part 6 Service Diagnosis
290
3.27 Indoor Blower Does Not Have Required Parameters to
Function
Applicable
Models
FXTQ-TA
Error Code
C6-02
Outline
Indoor units perform required settings for control on the fan motor, but if the minimum required
settings are not made then information indicating as such will be included among the periodic
control status information.
Error is issued when the information shows abnormality.
Error Decision
Conditions
If the parameter information shows abnormality, it will be deemed abnormal operation.
At that point, parameter settings when initializing the fan motor will be implemented from the
beginning.
Error Reset
Conditions
If the parameter information is normal, the error will be cleared.
Supposed
Causes
Locked motor rotor condition
Corrective
Actions
Check for locked rotor condition.
Replace the indoor unit PCB or motor.
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...