SiUS342303E
Troubleshooting by Error Code
Part 6 Service Diagnosis
368
Note(s)
Troubleshooting
Is
indoor-outdoor
and outdoor-outdoor unit
transmission wiring
normal? (
1)
Error is displayed
again?
Is
electricity
being introduced
for the first time after
installation or after an indoor
or outdoor unit PCB
has been
replaced?
Does
an error occur
even after 12 minutes
elapses from the time when
electricity is introduced
to indoor and
outdoor units?
NO
Replace the indoor unit control
PCB.
Does a
UH
error occur for all
indoor units in the
system?
NO
After fixing the incorrect wiring,
press the
RETURN (BS3)
button on the outdoor unit main
PCB for 5 seconds.
The unit will not run for up to
12 minutes.
NO
NO
Install the DIII-NET extension
adaptor.
YES
YES
NO
Normal
NO
Press the
RETURN (BS3)
button on the outdoor unit
PCB for 5 seconds.
YES
YES
Normal
YES
Replace the outdoor unit main
PCB (A1P).
YES
Disconnect
the outdoor-outdoor
unit transmission wiring to
create the one-system status,
and then check whether or
not the system is
normal.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
1. Refer to the installation manual for correct "indoor unit and outdoor unit
connection wiring”.
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...